Theatre ventilation setback under NETB 2026/1 - the BMS engineer's part
In July 2026 NHS England issued Estates Technical Bulletin NETB 2026/1, asking every trust with operating theatres to bring in overnight and weekend ventilation switch-off or setback (NHS England NETB 2026/1). It is one of the clearest, best-evidenced optimisation instructions the healthcare estate has had, and almost every requirement in it lands on the building management system.
This article is about the BMS engineer's part in that work. It is not a design guide and it does not replace the bulletin, HTM 03-01 or the trust's own procedures - read the bulletin itself before doing anything. And one point comes before all the others.
Governance first - this is never an integrator's decision alone
Theatre ventilation is a critical system. Any change to its schedules, setpoints, pressure regime or interlocks goes through the trust's Ventilation Safety Group (VSG), and day-to-day control of the system sits with the Authorised Person (Ventilation), with the Authorising Engineer (Ventilation) advising the group independently. The bulletin expects a project team that brings in infection prevention and control, theatre staff, the energy manager, finance and - in PFI hospitals - the PFI partner, who usually controls BMS changes there.
An integrator's role is to assess what the BMS can do, propose how it would do it, make the agreed changes under the trust's permit and change processes, and provide the evidence. It is never to decide that a theatre can be set back. Say this plainly in any proposal: a technical change should only be made by competent people, under the trust's governance, after the VSG has approved it.
Why the bulletin matters
The bulletin estimates savings of 132-286 MWh per theatre per year, and more than £43m a year across the NHS, from modelling published by Eames and colleagues in 2025. Theatres are several times more energy intensive than the rest of a hospital, and HVAC accounts for most of their energy. The bulletin notes that HTM 03-01 already allows setback, but that it has not been widely adopted - plant often runs at full output overnight in the belief that this protects sterility, although airborne contamination in a theatre comes from the people in it.
According to the bulletin, implementation cost runs from nothing for a simple schedule change to a few thousand pounds for full integration with the BMS and smart theatre panels.
| Conventional theatre, no heat recovery | |
|---|---|
| Full time | 357 MWh - £38k |
| Setback in the evenings | 225 MWh - £25k |
| Off in the evenings | 145 MWh - £16k |
| Setback evenings and weekends | 104 MWh - £12k |
| Conventional theatre, heat recovery (effectiveness 0.5) | |
| Full time | 212 MWh - £27k |
| Off evenings and weekends | 62 MWh - £9k |
| Ultra-clean ventilation (UCV) theatre, no heat recovery | |
| Full time | 408 MWh - £51k |
| Setback in the evenings | 261 MWh - £34k |
| Off evenings and weekends | 122 MWh - £17k |
Any change to theatre ventilation goes through the Ventilation Safety Group and the Authorised Person (Ventilation).
These are modelled figures, not measured trust results - the bulletin is only a few months old. They show the scale, and they are a sound basis for a business case, but a pilot with sub-metering is what turns them into a number for a particular theatre.
The three control strategies
The bulletin describes three ways to run a theatre's ventilation down when it is not needed. In summary, in our own words:
- Basic timed control. The plant starts a set time before the list and stops at an agreed time, with an audible and visual warning before the end of the session. It suits day surgery and elective hubs with predictable lists, and is not for emergency theatres.
- Timed control with overrun. As above, plus an extend button on the surgeon's panel and a way to start the system manually out of hours.
- Occupancy-based control. Sensors (passive infrared, radar or thermal people counting) keep the plant running while the room is in use and for a period after it empties, set it back in the day when unoccupied, and switch it off out of hours. This may not suit some theatres - the bulletin notes that continuous running may be the safer choice for emergency obstetric theatres.
Which strategy suits which theatre is a clinical and VSG decision. The BMS engineer's job is to say which ones the existing system can support, what would need adding, and how each would be tested.
What the BMS has to do
Whichever strategy is chosen, the bulletin's requirements translate into a short list of BMS functions:
- Hold a safe temperature band. While a theatre is off or set back, its temperature must stay within a band (16-25°C in the bulletin) to avoid condensation and mould at the cold end and damage to drugs and equipment at the warm end. If the space drifts outside it, the BMS restarts the AHU in setback.
- Interlock the anaesthetic gas scavenging (AGSS) pumps with the AHU so they stop and start together - each pump draws several hundred watts - and interlock ultra-clean ventilation canopy fans the same way.
- Map which AHU serves which theatre. One AHU may serve several theatres, and anaesthetic rooms may have their own plant. The map has to be right before anything is switched, or setback in one room can cause backflow in another.
- Protect the pressure cascade. Do not ventilate an anaesthetic room while its theatre's AHU is off, and keep the flow of air from clean to less clean areas.
- Show a clear status on the theatre panel - text, or a simple colour for off, setback and full running - so theatre staff always know the state of the room.
- Allow time to recover. After a long switch-off the bulletin gives the ventilation time a theatre needs before it is safe to use, which is shorter than the time needed to prepare for an emergency case. The start-up logic and any manual start have to respect it.
Each line becomes a point to check on the existing system, a sequence to write or amend, and a test to witness.
Capability first, then a pilot
The bulletin is frank that not every BMS will be up to this, and that in some cases upgrading it may be cost effective. A sensible order of work:
1. Survey what exists. Controllers, spare inputs and outputs, panel types, existing interlocks, sensors in the theatre and the plant, and the state of the AHU, dampers and heat recovery. The BMS health check covers the general method. 2. Baseline the energy. Sub-metering on the theatre AHUs, logged long enough to show a normal pattern, so the change can be measured under IPMVP rather than estimated. Proving savings explains the options. 3. Propose, then pilot. A written proposal to the VSG covering the strategy, interlocks, temperature band, panel status, failure modes and back-out. The bulletin strongly advises a technical pilot on one theatre before rolling out. 4. Verify at both speeds. Annual verification should measure the system at full speed and in setback. If pressure differentials fall short of the bulletin's tolerance against design, investigate and re-verify.
Faults that get in the way
The bulletin lists the conditions that undermine both air change rates and energy: ageing AHUs, manual or outdated controls and setpoints, dampers set wrongly or failed, sensors and actuators out of calibration, clogged filters, high-grade filters fitted without the system being re-balanced, and poorly maintained heat recovery. A setback project usually turns some of these up, so allow for remedial work in the programme rather than discovering it during the pilot.
Carbon, and how to report it
Theatre savings are a mix of electricity (fans) and heat. When reporting carbon, state the conversion factor year. The 2026 UK government grid electricity factor is about a quarter lower than the 2025 one, so the same electrical saving counts for less carbon on paper - something worth explaining to an energy manager before the report lands.
Further reading
Which HTM governs which BMS point maps the wider hospital duties, and BMS cyber hygiene evidence covers what an NHS client's security lead will ask about remote access. BMS before heat pumps sets theatre work in the context of estate decarbonisation, and Commissioning a BMS covers witnessing and handover.
Related tools and training: the out-of-hours running cost, heat recovery savings and CUSUM tools are in tecTools, and the AHU commissioning and Servicing and optimising an existing BMS courses are in tecTraining.
Published guidance mentioned: NHS England NETB 2026/1, Generating energy efficiency savings through controlling theatre ventilation (July 2026), which supplements HTM 03-01 (2021); modelling by Eames et al. (2025). Figures quoted from the bulletin are modelled. Any change to theatre ventilation needs the Ventilation Safety Group's approval and the Authorised Person (Ventilation)'s control.