Frost, safeties and the first cold night - what to prove on an AHU before winter

The first properly cold night of the winter finds every weakness in an air handling unit's frost protection. By morning the call has come in: the AHU has tripped on frost, the offices are cold, and someone wants to know why the BMS let it happen - or why it will not reset. Some of those trips are the protection doing exactly its job. Others are a wrong setting, a damper that leaks, a valve that never reached full open, or a device that was bridged out years ago and forgotten.

This article is for integrators and service engineers who look after AHUs, and for the FM teams who take the calls. It covers what frost protection is for, the two different jobs it does, and what a controls engineer should prove before winter. It does not tell you what setting to use or what action the plant should take - those come from the design, the AHU maker and the control description.

Two jobs that get mixed up

Coil frost protection stops the water in a heating or preheat coil from freezing and splitting the tubes. A frozen coil is expensive, it floods the AHU when it thaws, and the unit is out of service while it is replaced.

Heat recovery defrost keeps a plate exchanger, wheel or run-around coil working when moisture in the extract air freezes on the cold side. Ice blocks the passages, pressure drop rises and recovery falls away. Heat recovery that recovers covers the three kinds of exchanger.

They use different sensors and take different actions, and they are often confused on drawings and in alarm text. Approved Document L asks for defrost control on heat exchangers, and for a way to stop, modulate or bypass recovery when it is not wanted, in paragraph 5.60 of the 2026 edition of Volume 2 (6.56 in the 2021 edition). For how either job is done, much of the published detail comes from Eurovent Recommendation 6/17, which is European industry guidance rather than a UK requirement.

How a coil frost scheme usually works

A common arrangement uses a temperature sensor or an air-side frost thermostat close to the coil, and acts in stages as the air temperature falls:

Sources differ on the detail. Eurovent describes an air-side thermostat with its sensing element downstream of the coil, stopping airflow below the limit, and starting the fans in a cold start only once the heater is at full output. Some North American practice puts the element upstream and adds damper and valve actions; the freeze protection sequence in ASHRAE Guideline 36, as published in the Modelica Buildings Library documentation, stages software action before a shutdown. UK healthcare guidance sets out the valve split - the frost coil's valve goes open on a frost trip, while other heater valves close on airflow or fan failure - in HTM 03-01 Part A, paragraphs 9.212 and 9.223. Where the design and the product instructions disagree, raise a query rather than choosing one.

Heat recovery defrost - and its price

For a heat exchanger, the question is when freezing will start. Outside air temperature is the simplest trigger, but real freezing depends on how moist the extract is, so early defrost wastes energy and late defrost lets ice build. Better schemes look at the exhaust temperature at the critical point, extract humidity, or the pressure drop across the exchanger.

Every defrost action costs something. Preheating costs heat. Bypassing a plate puts load on the heater. Slowing a wheel loses recovery. Cutting the supply fan while the extract runs can pull the building into negative pressure. Which trade-off is right is a design decision. The controls engineer's job is to prove that the chosen action happens when it should - and that it stops again afterwards.

What to prove before winter

The order of proving safeties - wiring checked, then devices operated with fans off, then with fans running at low speed - follows published practice such as CIBSE Commissioning Code C. Work under your method statement, with someone in charge of any override, and log it.

What stays outside the controls engineer's remit: choosing the method, changing a setting, or leaving a frost device overridden to stop nuisance trips.

When it trips anyway

A frost alarm that repeats is telling you something about the plant, not only the device. The usual suspects:

Trend the off-coil temperature, valve position, pump status, damper position and outside air temperature through the first cold fortnight. A trip that comes at the same time every morning is usually a start-up sequence; one that comes on the coldest night alone may be the protection doing its job. Psychrometrics helps check what the air is doing across the coil.

Make it part of autumn readiness

Frost protection belongs on the autumn visit, with pump exercise, heating lockouts, compensation curves and summer overrides - see Seasonal changeover for the full list and The BMS service visit for where it sits in the year.

Sources mentioned: Approved Document L, Volume 2, 2026 edition paragraph 5.60 and 2021 edition paragraph 6.56; Eurovent Recommendation 6/17 (2021), sections 4.4 and 5.3.1 (European industry guidance); ASHRAE Guideline 36 freeze protection as documented in the Modelica Buildings Library; HTM 03-01 Part A (NHS England, 2021), paragraphs 9.212 and 9.223; CIBSE Commissioning Code C (2001). Settings and actions here are examples - the design, the AHU maker's instructions and the control description decide.