Heat recovery that recovers - plates, wheels and run-around coils
Heat recovery is one of the largest single energy measures on an air handling unit. It is also one of the easiest to lose without anyone noticing. A bypass damper stuck open, a wheel whose belt snapped two winters ago, a run-around pump that never got an enable, a frost strategy that bypasses all day in November - the unit still runs, the space is still comfortable, and the heating coil quietly does the work the recovery was bought to do.
This article is for integrators and engineers who commission or service air handling units, and for FM teams who want to know whether their recovery is earning its keep. It covers the three common types, what Approved Document L asks of their controls, the frost and bypass duties, and how to prove recovery is really happening.
What Approved Document L asks
Approved Document L Volume 2 (2026 edition, taking effect on 24 March 2027) says supply and extract ventilation systems should be fitted with heat recovery where technically feasible (5.63), and that heat exchangers should have defrost control to protect them, plus control so recovery can be stopped, modulated or bypassed when it is not wanted (5.60) (Approved Document L Volume 2, 2026). The 2021 edition carried the same control duties at 6.56 (Approved Document L Volume 2, 2021 with 2023 amendments).
So every recovery device needs two control functions: protection from frost, and a way to back off. How each type does them differs.
Plates - control by moving the air
A plate exchanger passes extract and supply air on either side of thin plates, with no moving parts. It is controlled by moving air around it: face and bypass dampers send part of the outside air through the plates and the rest round them. Bypass usually does both jobs - backing off and frost protection. The European Ecodesign rules for ventilation units (Regulation (EU) 1253/2014) also expect a thermal bypass on non-residential units of this kind; check how that applies in Great Britain (legislation.gov.uk).
Plates are the type Eurovent's guidance on air handling unit controls calls most sensitive to icing (Eurovent Recommendation 6/17). Extract air cooled through the plates can drop below freezing at the cold corner, and air leaving a plate is far from uniform, so the exhaust-side sensor must sit at the most critical point. A sensor in the wrong place protects nothing, or defrosts for no reason. Proportional bypass sends only as much outside air round as needed; a full bypass needs a heater big enough to lift all of it, which is a design matter. Extract air also condenses on the plates, so the drain and siphon must be right before any of this is tested.
Wheels - control by speed
A thermal wheel carries heat, and sometimes moisture, by rotating between the two airstreams. It is controlled by speed: faster for more recovery, slower or stopped to back off, and slowed or paired with a pre-heater for frost.
Wheels need two extra checks. First, rotation: a command at 100% says nothing about a wheel that is not turning. If a rotation sensor is fitted, stop the wheel and check the alarm - and remember a slow wheel passes the sensor rarely, so the alarm delay must suit the lowest speed. Second, leakage: Eurovent names rotary exchangers as the type most prone to internal leakage from exhaust to supply, depending on the pressure difference across the two sides, and asks for a suitable difference in all operating states. Check the pressure relationship at more than one fan speed and report what you find to the commissioning specialist or the unit maker.
Run-around coils - control by pump and valve
A run-around system has a coil in each airstream, joined by a pumped loop of water and glycol. There is no leakage between the airstreams, which suits labs and hospitals, but there is water to look after. Control is by the pump and a three-way valve: the pump runs only when recovery is wanted, and the valve modulates or recirculates the loop. Eurovent lists recirculation through the three-way valve as a run-around frost method, and describes air leaving the coil as uniform, so sensor position is less critical than on a plate. The glycol mix belongs to the mechanical contractor - too much hurts performance and too little risks frost damage.
Backing off - and recovering cooling
Recovery is not always wanted. On a mild day with the space needing cooling and extract warmer than outside, recovery would add heat the cooling coil then has to remove - so it should give way. The opposite case is easy to miss: when outside air is warmer than the extract and the space needs cooling, some sequences drive recovery back to full, so the cool extract pre-cools the hot supply. The control action reverses as the two temperatures cross. Check the control description for which applies, and prove both edges.
A typical sequence runs along one demand signal - full cooling, deadband, heat recovery, then the heating coil - with no overlap of heating and cooling unless dehumidifying needs it. UK healthcare guidance says the logic should stop the cooling coil and heat recovery or heater running together (HTM 03-01 Part A, 9.215) (NHS England). Test the edges of each stage; that is where sequences go wrong.
Proving recovery happens
A status point is not proof. On a cool day with the extract warm, trend supply temperature after the exchanger while you stroke the bypass, change wheel speed or start the run-around pump. Air after the exchanger should warm when recovery increases. If it does not, check air is really passing through the plates or the wheel is really turning.
A rough effectiveness from the temperatures is a useful sense check: the rise in supply temperature divided by the difference between extract and outside. With outside at 2°C, extract at 21°C and supply after the plates at 16°C, that is 14 / 19, or about 74%. It is not a commissioning figure - use the figure in the project specification and the method it names - but a unit giving 30% where it should give 70% has a fault worth finding.
What to watch in service
Recovery faults rarely raise an alarm. A trend review catches them:
- Supply after the exchanger barely above outside temperature in winter - bypass open, wheel stopped, pump off.
- Bypass open on a cold day with no frost condition - a stuck damper or a frost setpoint set far too high.
- Frost mode all winter - the exhaust sensor in the wrong place, or a defrost setpoint copied from another unit.
- Heating coil working harder than last year at the same outside temperature - the recovery has quietly stopped.
Five trend charts that find the waste shows how to spot this on an AHU's air states, and the stuck economiser damper in Fault detection on a BMS is a close relative.
Who does what
The BMS engineer proves the bypass, the speed, the pump, the sensors and the sequence, and records frost setpoints from the design. The BMS engineer does not clear a blocked drain, adjust seals, belts, purge sectors or glycol, move a frost sensor because it looks wrong, or change the frost method - those go back to the mechanical contractor, the unit maker or the designer. Where the unit has packaged controls, the BMS may only send an enable and read a status; check the plan.
Sources mentioned: Approved Document L Volume 2, 2026 edition (5.60 and 5.63) and 2021 edition (6.56); Eurovent Recommendation 6/17 (European guidance, not UK requirements); Regulation (EU) 1253/2014 - the GB position on its bypass and efficiency requirements was not confirmed for this article; HTM 03-01 Part A (NHS England, 2021), 9.215. Diagram and effectiveness figures are illustrative.