Autumn readiness: five checks before the heating season

Frost protection, heat source sequencing, compensation curves, optimum start and pump exercise - five BMS checks before the first cold morning.

The first cold morning of autumn tests everything the BMS has not had to do since spring. A short readiness visit before the heating season protects the plant and avoids the "the heating is not on" calls.

1. Frost protection

Check frost thermostats, frost setpoints and the routine that runs pumps and opens valves in cold weather - and prove it acts. A frost routine that has never been tested is an assumption.

2. Heat source sequencing

Confirm boilers or heat pumps start, stage and rotate as designed, and that lead and lag changes happen. Plant that sat idle all summer should be started under the manufacturer's procedure by whoever is responsible for it.

3. Weather compensation

Compare the compensation curve with last winter's trends. Rooms too warm on mild days or too cold on cold days usually mean the curve needs adjusting - and many have not been touched since handover.

4. Optimum start

Check the learning or adaptive settings. Some controllers need several days of heating weather to relearn, so expect preheat times to move early in the season.

5. Pump exercise and summer overrides

Make sure pump exercise routines are enabled and actually ran over the summer, and clear anything left in hand - cooling forced on, heating forced off - so the heating lockout releases when it should.

Autumn is also a good moment to look back at the summer: standing alarms that built up, sensors that failed in the heat and any comfort complaints the facilities team logged. Clearing them now means the heating season starts from a clean slate.

Write down what you changed, with before and after values, and keep a few trends running into the first fortnight of heating. Our article Seasonal changeover covers the full autumn and spring lists, and the tecTools weather compensation and degree-day calculators help put figures to the results.

Read the changeover guide