Variable-speed pumping - where the DP sensor goes and when to reset it

Variable-speed pumps are now standard on heating and chilled water circuits. Approved Document L expects them, and every drive brochure quotes the cube law. Yet trend logs from occupied buildings often show the same thing: a pump that barely changes speed from morning to night, holding a pressure that was set on commissioning day and never looked at again. The drive is there; the saving is not.

This article is for integrators and engineers who commission or service variable flow systems. It covers why the textbook figures overstate real savings, where the differential pressure (DP) sensor goes, how a setpoint should be found and handed over, and how a most-open-valve reset gets close to the saving the drive was bought for.

What the rules ask for

Approved Document L Volume 2 (2026 edition, taking effect on 24 March 2027) says variable volume systems should use variable speed glandless circulators, that a closed-loop pump on a variable volume system with a motor over 750 W should have a variable speed controller, and that pumps should be selected following CIBSE Guide B1 and not oversized (paragraphs 5.48 to 5.50) (Approved Document L Volume 2, 2026). The regulation asks for the drive. What it saves depends on the controls.

The affinity laws - and why they flatter

For a centrifugal pump, flow follows speed, head follows speed squared and power follows speed cubed. At 80% speed the ideal is 80% flow, 64% head and about 51% power; at 50% speed, 12.5% power. The Hydraulic Institute and Europump guide sets out these laws and the case for speed control over throttling (HI and Europump, 2004).

Those figures hold only for a system whose curve passes through zero - pure friction - with efficiency unchanged. A closed heating or cooling circuit has no static lift, but holding a DP setpoint has much the same effect: the pump cannot slow below what the setpoint needs. BSRIA's guidance on variable flow systems explains why real savings fall short of theory (BSRIA AG 16/2002).

The same pump at half flow - ideal against a pressure held - Hydraulic power, kW (10 l/s at 200 kPa at design)
Design flow at 200 kPa2 kW
Half flow, design pressure still held1 kW
Half flow, pure friction (the cube law ideal)0.25 kW

Hydraulic power is flow times pressure. Holding the design pressure at half flow keeps half the power; a reset that lets the pressure fall recovers much of the rest.

The same pump at half flow - the cube law ideal against a pressure held at its design value. Source: Affinity laws as set out by the Hydraulic Institute and Europump (2004); worked example with pump efficiency held constant. Flags: Worked example, Efficiency held constant. Links: HI and Europump guide.

Where the sensor goes

The usual control holds a DP as valves close: the reading rises and the drive slows the pump. There is no single rule for where to sense it, and sources differ:

Follow the design. One point is clear from published guidance: the pump's sensor must sit outside the influence of any differential pressure control valve (DPCV), because a DPCV holds its own pressure steady and hides exactly the change the pump needs to see (Modern Building Services). If the sensor location looks wrong, raise it before the setpoint is recorded.

Finding the setpoint

The aim is the lowest setpoint that still does the job. On the critical valve's circuit, the commissioning specialist lowers the pump speed until the pressure across that valve sits just above its start-up pressure, records the branch flow, then reads the system sensor. That reading becomes the setpoint. In the usual split, the commissioning specialist finds it and the BMS engineer holds it - in the BMS or the drive, as the design says.

Then prove it at part load by trend: as valves close, the DP should hold and the speed should fall. Set a minimum speed from the pump and motor data, keep a water path if every valve can shut (or stop the pump when nothing needs it), and respect any minimum flows the boiler or chiller maker sets. Good DP control does not rescue a badly sized control valve - Valve authority, Kvs and characteristics covers why.

Most-open-valve reset

A fixed setpoint is chosen for the design day. On every other day most valves are part closed and the pump is still delivering the pressure the worst day needed. A reset strategy lets the BMS find a lower setpoint continuously:

The effect is that the pressure falls to the lowest value that keeps every valve in control, and the sensor's position matters much less. Pump makers now offer proportional pressure modes that lower the setpoint as flow falls; a BMS reset goes further because it knows what each valve is asking for. Record which mode is set, the limits, and whether the pump or the BMS owns the setpoint.

Reset is not a fix for a bad valve. A valve that is wildly oversized or has failed open will hold the setpoint down, and one zone that never satisfies will drive it up all day. Exclude a faulty valve from the reset only as a recorded, temporary measure while it is repaired - and tell the client.

Why the saving is often missing

On real sites, the usual reasons are mundane:

A trend of pump speed, DP and the most-open valve over a week shows most of these at a glance. A pump whose speed hardly moves while the valves swing is the first thing to look at.

Fault order when a coil runs short

When a loop will not settle or a coil runs short, more pump is rarely the answer. Work in order: air and dirt clear, the valve in its control range, the branch flow, then the temperature difference across the coil - and only then the pump speed. Raising flow to cover a shortfall usually makes low delta-T worse.

Handover and evidence

Approved Document L asks for a notice of completion of commissioning that confirms test results are reasonably in line with the design, with written commentary where a service falls short (2026 edition, paragraph 7.7). For pumping, keep the setpoint, who found it and how, the minimum speed, the control mode, and a trend at part load showing the speed falling. A record like that lets the next engineer tell a deliberate setting from a forgotten one.

Sources mentioned: Approved Document L Volume 2, 2026 edition (5.48 to 5.50 and 7.7); Hydraulic Institute and Europump guide (2004); BSRIA AG 16/2002 and BG 12/2011; Modern Building Services on pump sensors and DPCVs (trade press, a valve maker's author). Chart and diagram figures are illustrative, with pump efficiency held constant; use the pump curves and measurements for real estimates.