Valve authority, Kvs and characteristics - why tuning cannot fix a badly sized valve
Every controls engineer has met the loop that will not settle. It holds well on a cold morning with the valve half open, then on a mild afternoon, with the valve barely cracked, it starts to swing - shut, open, shut - and the room temperature follows. The usual response is to retune: less gain, more integral time. Sometimes that helps. Often it just makes the loop slow at full load without curing the swing at light load, because the problem is not in the controller. It is in the valve.
This article is for integrators and commissioning engineers, and for the M&E and FM teams who specify and maintain the plant. It explains Kv and Kvs, valve authority and valve characteristics in plain terms, shows why a badly sized valve puts most of its control into the last few percent of travel, and sets out what to check before reaching for the tuning. Valve selection is the designer's job; the controls engineer's job is to recognise when the hardware is the cause.
Kv and Kvs - what the valve passes
Kv is a flow coefficient: the flow of water in cubic metres per hour that passes with 1 bar across the valve. It changes with the valve's opening. Kvs is the figure at full travel - the number on the data sheet. With flow Q in m³/h and pressure drop in bar, the drop across the valve is (Q / Kv) squared, so doubling the flow quadruples the drop.
Two points follow. First, pipe size does not tell you capacity: one body size is often sold with several Kvs values, and a valve chosen to match the pipe is often far bigger than the duty needs. Second, Kvs values come in steps - 4, 6.3, 10, 16, 25 and so on, each about 1.6 times the last - so one step either way changes the pressure drop at the same flow by roughly two and a half times. Choosing between neighbouring sizes is really a choice about authority.
The flow coefficients and characteristics are defined in BS EN 60534-2-4 and the rest of the 60534 series.
Authority - does the valve get a say?
A valve can only control flow if it takes a real share of the pressure in the circuit it controls. Valve authority measures that share: the drop across the fully open valve at design flow, divided by that drop plus the drop across the rest of the circuit whose flow the valve varies.
- For a two-port valve, the rest of the circuit runs back to the nearest point of held pressure - the pump, or a differential pressure control valve if there is one.
- For a three-port valve diverting round a coil, it is mainly the coil, so a valve drop equal to the coil drop gives about 0.5.
- For a mixing valve feeding its own pumped circuit, it is the primary pipework between the valve and the header or heat source, not the emitters.
BSRIA BG 51/2014 covers valve selection in variable flow systems. Around 0.5 is the usual target, though guidance varies and many treat anything under about 0.25 as poor. Follow the design where it gives a figure. Higher authority is not free: every kilopascal across a valve is pump head at design flow.
### A worked example
Take a heating coil of 45 kW on a 20 K temperature difference. It needs about 1.9 m³/h. Say the rest of its variable-flow circuit drops 15 kPa.
- Kvs 4 drops about 23 kPa - authority about 0.6.
- Kvs 6.3 drops about 9 kPa - authority about 0.4.
- Kvs 10 drops under 4 kPa - authority about 0.2.
If the pipe is DN25 and the valve was simply picked to match it, Kvs 10 is a likely result. It will pass the flow happily at full load. At light load it will hunt.
Characteristics - and why coils need them
A valve's inherent characteristic is how its Kv changes with travel at a steady pressure. On a linear valve, equal steps of travel give equal steps of Kv. On an equal-percentage valve, each equal step multiplies the Kv by the same factor, so the first half of the travel passes surprisingly little.
That shape is deliberate. A hot water coil gives a large share of its output at small flows: depending on the coil and its water temperatures, around a tenth of design flow can give somewhere between a quarter and a half of full output. An equal-percentage valve offsets that, so output follows valve position more evenly - which is why it is the usual choice for water coils. The ASHRAE Handbook - HVAC Systems and Equipment and K. W. Peterson's ASHRAE Journal article on selecting modulating control valves (February 2017) set out the reasoning.
Low authority undoes the characteristic
Once installed, the valve is in series with the rest of the circuit. As it closes, it takes more of the available pressure, so flow falls more slowly than the inherent curve suggests. The lower the authority, the more the installed curve bows upwards - towards a quick-opening shape.
On an idealised equal-percentage valve with a 50:1 range, half travel passes about 14% of design flow with an authority of 1, about 20% at 0.5, about 27% at 0.25 and about 41% at 0.1. Put a coil after it and the effect compounds: at an authority of 0.1, the first fifth of the travel can deliver around half the coil's output.
That is the hunting loop. A loop tuned at full load, where a 10% change in signal moves the output a little, meets a region at light load where the same 10% moves it a lot. The loop gain has jumped, and the controller overshoots. Turning the gain down to suit light load makes it sluggish everywhere else. No single tuning suits both.
What to check before retuning
1. Read the valve label and data sheet. Kvs, characteristic, and the actuator's stroke time. Compare the Kvs with the design flow and the pressure drop it should take. 2. Work out the authority roughly. Design flow and Kvs give the valve drop; the drawings or a commissioning record give the circuit drop. The valve and damper sizing tool does the arithmetic. 3. Look at the trend. Is the valve spending most of its time below 20% open? Is the swing worse at light load? Does the valve-to-temperature relationship look steep near closed? 4. Check the differential pressure. On a two-port system with a fixed-speed pump, the pressure across a closing valve rises at part load, so true authority is lower than the design figure. A pump that is never reset, or a DP sensor in the wrong place, makes it worse. 5. Check the actuator and rangeability. A valve asked to control below its smallest controllable flow will step between shut and just open whatever the tuning.
If the valve is the cause, the honest answer is a hardware one - a smaller Kvs, a pressure-independent valve, or differential pressure control - and that goes back to the designer. Tuning can then do its proper job, which is to make a sound loop respond well, not to hide an oversized valve.
Oversized valves also feed low delta-T.
Sources mentioned: BS EN 60534-2-4 (inherent flow characteristics and rangeability); BSRIA BG 51/2014, Selection of control valves in variable flow systems; ASHRAE Handbook - HVAC Systems and Equipment (2024); K. W. Peterson, Considerations for selecting modulating control valves, ASHRAE Journal (February 2017); the BCIA guide Selection of Control Valves (2021). The example figures and curves are idealised - real valves and coils follow their makers' data, and valve selection belongs to the designer.