Pools after the support fund - getting the new kit to work together
Swimming pools are the most energy-intensive buildings most councils own, and they were hit hardest when prices spiked in 2022-23 - operators reported bills up to 200% higher than in 2019 (Swim England / ukactive). Many pools have since had new kit paid for by public money. Whether that kit saves what it was bought to save now depends largely on the controls.
This article is for integrators who look after leisure centres. It covers what the support fund paid for, the handful of control settings that decide a pool hall's energy, the faults that hide behind them, and how to show the funded measures are working.
What the fund paid for
Phase II of the Swimming Pool Support Fund in England was worth £60m - £40m from government and £20m from the National Lottery - and was run by Sport England for DCMS. Sport England reported more than 500 capital measures in over 300 pool facilities (Sport England). Its stated aim was to cut energy use and carbon against a baseline.
Council papers show what typically went in: solar PV, energy-saving showers, variable speed filtration pumps, pool covers and LED lighting (West Oxfordshire District Council). Published results are thin. Aldershot Pools reported around a 20% cut in electricity use, though the baseline method was not stated (Rushmoor Borough Council). Other figures in public papers are projections made before the work. No fund-wide measured evaluation has been published.
| Reported after the work | |
|---|---|
| Aldershot Pools - electricity use (baseline method not stated) | about 20% |
| Formby Pool - extra solar, share of grid electricity offset | 11% |
Phase II (£60m) funded more than 500 measures in over 300 pool facilities. No fund-wide measured evaluation has been published - so verifying the funded kit works together is the service.
That gap is the opportunity. New pumps, covers and heat pumps installed in 2024 and 2025 need integrating with the existing BMS, tuning through the seasons and verifying. An integrator who measures before and after, with the operator's permission, is filling a real hole in the evidence.
The settings that decide a pool hall's energy
A pool hall loses heat mainly by evaporation, and evaporation depends on the difference between the water and the air above it. Four settings matter most.
- Air-to-water offset. Hall air is usually kept a little warmer than the water to hold evaporation down. Trade guidance gives 1-2 K (Pool & Spa Scene). Sport England's pool design guidance gives water at 28°C for competitive and fitness pools and hall air at about 30°C (Sport England). Treat these as guidance and check the design basis for each hall.
- Humidity setpoint and reset. The humidity the hall is held at decides how hard the dehumidification plant works and whether cold surfaces condense. A Loughborough University case study (2006) described a BMS resetting the humidity setpoint against outdoor temperature (AUE case study) - older, but the principle holds. The right setpoint for a hall belongs to its designer; the commonly quoted figures could not be confirmed against the primary design guidance.
- Heat recovery. Dehumidifying by cooling lets the condensation heat be put back into the pool water or the air. A vendor estimate suggests recovery can cut air heating and pool water energy by about half - a vendor figure, so use it as a reason to check, not a promise.
- Out-of-hours operation. With a cover on, evaporation falls sharply, so fresh air, fan speeds and heating can all be turned down - within the limits set by the water treatment regime.
Why cutting the air temperature can backfire
The most common false economy in a pool hall is lowering the air temperature to save heating. If the air drops below the water, evaporation rises, humidity climbs, the dehumidifier runs flat out and glazing and structure start to condense. Plant sized for a comfortable offset may struggle when the offset shrinks. The heating saved can be smaller than the dehumidification and condensation cost.
The fingerprint on the trends is easy to find once you look: air-to-water offset falling, then relative humidity and dehumidifier duty climbing together. Trend hall air, water temperature, humidity and dehumidifier output on one chart for a week.
Faults that hide behind the new kit
From the controls literature and field experience, rather than a measured UK dataset, these come up again and again in pool plant:
- Heat recovery bypassed. A bypass damper stuck open or a run-around pump left off, so the recovery device does nothing while the trend still shows the plant running.
- Variable speed pumps at full speed. A drive left in hand at 50 Hz, or turned down only in theory. Filtration turndown out of hours must stay within water treatment guidance - agree the limits with the pool operator and whoever is responsible for water quality before changing anything.
- Covers without a cover mode. The cover goes on, but the hall's air handling and heating carry on as if the pool were open.
- Fighting plant. Air heating and dehumidifier reheat working against each other, or two units with drifted humidity sensors doing opposite jobs.
- Calorifiers and pool heat exchangers on the wrong time. Scheduled for the old opening hours, or heating water that nobody will use until morning.
A good reference point is Woodside Leisure Centre in Watford, where the hall air is held 1 K above the water, plate heat exchangers recover both sensible and latent heat, and the air handling units switch off above 22°C outdoors in summer (MODBS).
Verifying the funded measures
Councils and trusts that took fund money committed to cutting energy against a baseline, and a scrutiny committee will eventually ask whether it worked. A short verification package answers that:
1. Agree the baseline. Meter data from before the work, adjusted for weather and opening hours. 2. Check each measure is doing its job. Pump speeds out of hours, cover mode, heat recovery effectiveness, solar export and self-use. 3. Tune the interactions. The settings above, with the operator's and water treatment adviser's agreement. 4. Report the result. A before-and-after comparison with its method stated, so the figure stands up to scrutiny.
Proving savings covers the measurement options, and BMS before heat pumps covers getting controls right for the heat pumps that many leisure sites are now taking.
Shaping the offer
A pool service built on this might include a seasonal controls review, a cover-mode and out-of-hours check, heat recovery and dehumidifier performance checks, sensor calibration for humidity and water temperature, and a short annual verification report. Keep water treatment and pool safety where they belong: with the operator and its specialists.
Related tools and training: the pool hall setpoint checker, the psychrometrics, heat recovery savings, inverter (VSD) savings and CUSUM savings tracker tools are in tecTools, and the Servicing and optimising an existing BMS course is in tecTraining.
Sources mentioned: Swim England and ukactive energy survey; Sport England on the Swimming Pool Support Fund; West Oxfordshire and Rushmoor council papers (2024); Pool & Spa Scene (trade guidance - indicative); Sport England swimming pool design guidance (2013); Health Club Management (2025) on Formby Pool; AUE case study of Loughborough University (2006, older data); MODBS on Woodside Leisure Centre. Humidity setpoints and offsets are not confirmed against the primary design guidance - check the design basis for each hall.