Measurement you can defend - calibration, accuracy and CO2 and humidity sensors
Every control loop, every energy report and every compliance trend rests on a handful of sensors. When a client, an auditor or a school's head teacher questions a number, the answer cannot be "that's what the BMS says". It has to be: this is how it was measured, this is what it was checked against, and this is how far it can be trusted.
This article is for integrators doing service and commissioning work, and for FM teams who rely on BMS figures as evidence. It covers the difference between calibration and adjustment, what an accuracy figure really means, the kinds of error and how to tell them apart, siting, and the particular traps in humidity and CO2 measurement.
Calibration is not adjustment
The two words are often used as if they meant the same thing. They do not.
- Calibration means checking what an instrument says against something you trust more, in steady and known conditions, and writing down the gap. The instrument is left as it was.
- Adjustment means altering the instrument, or the way its reading is handled, so the gap goes away.
A correction entered on a BMS point is therefore an adjustment, and it only stands up if a calibration came first and found an error that stays put. That means a reference that holds a current certificate, time for both readings to settle at the sensor itself, more than one reading, and a note of the values before and after. Entering an offset just because a reading looked wrong covers up whatever is really wrong, and leaves the next engineer a correction nobody can explain.
Meters used for billing are a different matter altogether. In Great Britain, water, gas, electricity and thermal energy meters used for trade fall under legal metrology law - the Measuring Instruments Regulations 2016, with GOV.UK statutory guidance. A billing heat meter is never "corrected" on the BMS.
Accuracy is not resolution
Most transmitter accuracy figures are quoted against the full span of the instrument rather than against what it happens to be reading. Take a 0-1,000 Pa transmitter with a stated accuracy of 1% of full scale: its error band is plus or minus 10 Pa wherever it is reading. Halfway up the range that is 2% of the value; near the bottom, at 100 Pa, it is 10%. A duct static loop running at 120 Pa on a 0-1,000 Pa transmitter is controlling on a figure that could be a long way off. Pick a range that matches the pressures the plant actually runs at.
Resolution is something else again - the smallest step the input can show. Divide a 0-1,000 Pa range into the 1,024 steps of a 10-bit input and each step is roughly 1 Pa; across a 200 K temperature span it is roughly 0.2 K. A graphic showing two decimal places tells you about the display, not the measurement.
Lead resistance and signal type matter too. A long cable run adds error to a resistance sensor, and a 4-20 mA loop carries a live zero that a 0-10 V signal does not - Signals that lie covers both.
Three kinds of error
Errors come in kinds, and each has its own cure:
- Offset - a steady error, the same every time. Once a calibration has found it, it can be corrected.
- Drift - an error that grows over months. An offset entered today will be wrong next year; the sensor needs re-checking on a schedule, or replacing.
- Noise - readings that scatter: electrical interference, turbulence, a poor connection. Averaging or filtering reduces it; an offset does not touch it.
There are two more to rule out before blaming the sensor. Installation error comes from where and how it is fitted. Lag comes from a slow sensor in a changing process: it reads behind the true value and shows smaller swings than really happen. Follow the reading from the process, through the sensor and its wiring, to the screen, and decide which link is at fault before changing anything.
Siting is half the accuracy
A sensor measures conditions exactly where it is. CIBSE Guide H covers sensor location in detail (CIBSE Guide H: Building control systems). A few points come up again and again on service visits:
- Room sensors mounted on an internal wall at roughly head height for people seated and standing, clear of heat sources, equipment, sun and draughts - and with the conduit or back box sealed so air from inside the wall cannot reach the element.
- Outside air sensors out of direct sunlight - usually a shaded north- or north-east-facing wall in the UK - and away from windows, flues and exhaust grilles. Sun on the housing can push the reading up by several degrees, which then misleads weather compensation and optimum start.
- Immersion sensors in a pocket deep enough that the sensing element sits fully in the moving water - reaching the pipe's centre line or beyond - and with conducting paste in the pocket rather than an air gap.
- Duct sensors where air is well mixed; an averaging element where the air layers, spread across the whole section.
Humidity depends on temperature
Relative humidity is relative to temperature. Using standard moist air properties, as tabulated in CIBSE Guide C, air at 20°C and 50% RH holds about 7.3 g of water per kg of dry air. Warm that same air to 22°C, adding and removing nothing, and it reads about 44% RH. So before blaming a humidifier for a falling RH trend, check what the temperature did. Where moisture content is what matters - a museum store, a pool hall - trend it directly, or calculate it from temperature and RH.
RH elements of the common capacitive type lose accuracy over time, so they belong on the calibration schedule. Humidity sensors also need to sit well downstream of humidifiers, at the distance the maker gives.
CO2 is a guide, not a verdict
CO2 is widely used to judge ventilation, and HSE's guidance on using CO2 monitors is the plainest UK reference. It says CO2 levels consistently above 1,500 ppm in an occupied room indicate poor ventilation and that action should be taken, while stressing that readings are a broad guide rather than proof of safe levels. It recommends non-dispersive infrared (NDIR) monitors, placed at head height, more than 50 cm from people and away from windows, doors and air supply openings, and warns that a single snapshot reading can mislead. Calibration follows the maker's instructions.
For context, the global average outdoor level is now above 420 ppm (NOAA Global Monitoring Laboratory), so an indoor reading of 400 ppm in an occupied room deserves a second look. Approved Document F asks for air quality monitoring in many new occupiable rooms, including offices, and where CO2 monitors are used they should be NDIR type (Approved Document F Volume 2, 2021 edition, 1.21-1.23). Monitoring is not the same as control: a sensor driving demand-controlled ventilation needs checking to a higher standard than one feeding a dashboard.
Some NDIR sensors re-zero themselves on the lowest level they see, on the assumption that the room returns to outdoor air when nobody is in. An office that empties every night suits that; a ward, a control room or a 24-hour space does not. The maker has to show their claim holds for the space. Schools are a special case, with their own CO2 criteria in Building Bulletin 101 - see Term time, holidays and CO2.
A calibration plan you can defend
A sensible plan, agreed with the client, lists the sensors that matter most - those driving energy-critical loops, those used as compliance evidence, those on billing or M&V - with the reference to be used, the check interval, the tolerance at which a sensor is adjusted or replaced, and who records the result. Every check is written down: date, reference instrument and its certificate, both readings, any adjustment made. That record is what turns a BMS number into evidence.
Sources mentioned: HSE, Using CO2 monitors; Approved Document F Volume 2 (2021 edition); the Measuring Instruments Regulations 2016 and GOV.UK statutory guidance; CIBSE Guide C (moist air properties) and CIBSE Guide H (sensor location); NOAA Global Monitoring Laboratory. Accuracy and resolution figures are worked examples; the sensor's data sheet sets the real ones.