Signals that lie - 4-20 mA live zero, 0-10 V loading and lead resistance

A good share of the "plant faults" a service engineer is called to are not plant faults at all. The valve is fine, the coil is fine, the fan is fine - the number on the screen is wrong. A broken wire reads as an empty tank, an actuator signal sags so the valve never quite opens, a temperature sensor reads three degrees high because of the cable it hangs on. Each one is believable, and each one can send a team chasing the wrong thing for weeks.

This article is for integrators and engineers who commission or service BMS inputs and outputs. It covers the three signal faults that most often pass for something else, the arithmetic that makes them visible, and the checks that separate a lying signal from a real fault.

4-20 mA - why the zero is live

A 4-20 mA signal carries the value as a current. 4 mA is the bottom of the range and 20 mA the top, a span of 16 mA. Because the same current flows all the way round the loop, the cable's resistance does not change the reading as long as the supply voltage is enough - which is why current signals cope well with long runs and electrical noise. The direct current signal ranges are set out in IEC 60381-1 (IEC).

Starting at 4 mA rather than 0 mA is called a live zero. It means a current of 0 mA can only be a fault - a broken wire, a blown fuse, a dead transmitter - never a genuine low value. Scaling is simple: value = low + (mA - 4) / 16 × (high - low). On a 0-50°C transmitter, 12 mA is half way along the span, so 25°C.

The trap is what the controller does with a current below 4 mA. Scaled blindly, 0 mA on a 0-100% level transmitter becomes -25%, and many inputs clamp that to 0%. A tank that reads empty, a duct that reads no pressure, a room that reads no CO2 - all plausible, all wrong.

The fault bands

NAMUR recommendation NE 43 standardises how a transmitter tells the system it has failed (NAMUR). As widely published:

Not every transmitter on a building follows NE 43, and makers' fail levels vary, so check the data sheet. Where the input allows it, set alarms on the bands rather than on the scaled value, so a failed loop is reported as "sensor fault", not read as 0%.

A loop also needs enough voltage. The supply must cover the transmitter's minimum voltage plus the drop across the cable and the input at 20 mA. With a 24 V supply and a transmitter needing 12 V, the loop can carry up to (24 - 12) / 0.020 = 600 ohms. A loop that reads correctly at low values and flattens near the top of its range is often running out of voltage.

0-10 V - a signal that depends on its load

A 0-10 V signal carries the value as a voltage, and it is everywhere: actuators, room units, drive speed references. 2-10 V is the voltage version of a live zero, where 0 V means a broken wire or lost supply. IEC 60381-2 covers the direct voltage ranges (IEC).

A voltage signal is only right if the source can drive what it is connected to. The output and the input form a potential divider: the input sees the source voltage × Rload / (Rsource + Rload). A typical input has a high resistance - often 10 kilohms or more - so one input draws very little current. Problems start when one output feeds several devices. Two 10 kilohm inputs in parallel are 5 kilohms; five of them are 2 kilohms. If the load falls below what the output is rated for, the voltage sags and every device reads low. A valve commanded to 75% that only ever reaches 68% looks like a sticking actuator or an undersized coil.

The second common error is a shared 0 V. Many 24 V AC actuators use one conductor for both the supply return and the signal reference. If 0.3 A of actuator current flows through 2 ohms of shared conductor, the reference shifts by 0.6 V - six per cent of the range. Use a separate signal reference where the actuator allows it, keep voltage runs short, and use 4-20 mA for long ones.

Lead resistance - the cable is part of the sensor

Most BMS temperature sensors are resistive: the controller works out temperature from the sensor's resistance. Anything else in series with the sensor - the cable - is added to the reading.

Copper has resistance. BS EN IEC 60228 allows up to 36 ohms per kilometre for a 0.5 mm² core at 20°C, and about 12.1 ohms per kilometre for 1.5 mm² (BSI). On a two-wire sensor the current goes out and back, so a 50 m run is 100 m of conductor.

What that does depends on how much the sensor changes per degree. A platinum PT100 changes by about 0.385 ohms per kelvin; a PT1000 by ten times as much (BS EN IEC 60751:2022). A 10k NTC thermistor changes by hundreds of ohms per kelvin near room temperature.

How far a two-wire sensor reads high on a 50 m cable run - Reading error from the cable alone, K (100 m of conductor, out and back)
PT100 on 0.5 mm² cores9.4 K
PT100 on 1.5 mm² cores3.1 K
PT1000 on 0.5 mm² cores0.9 K
PT1000 on 1.5 mm² cores0.3 K
10k NTC on 0.5 mm² cores (near room temperature)under 0.01 K

Worked from the maximum conductor resistance (36 ohms per km for 0.5 mm², 12.1 for 1.5 mm²) and the sensor's change per kelvin. A three- or four-wire connection cancels most of it.

How far a two-wire sensor reads high on a 50 m run, worked from the conductor and sensor standards. Source: BS EN IEC 60228 conductor resistance at 20°C; BS EN IEC 60751:2022 platinum sensor sensitivity (about 0.385% per kelvin); NTC slope typical of a 10k thermistor. Flags: Worked example, Two-wire connection. Links: BSI - BS EN IEC 60228, BSI - BS EN IEC 60751.

The answer is in the wiring and the sensor choice:

Noise, screens and segregation

Some signals lie intermittently. Use screened cable for analogue and network signals and earth the screen at one end only, usually the panel, so no current flows in it. Keep signal cables apart from mains and especially drive output cables, cross them at right angles, and never share a multicore between low voltage signals and mains. A reading that jumps when a fan starts is telling you about the cable route.

Proving the signal, not the plant

Before blaming plant, prove the signal path from the process to the screen:

The common thread is simple: the number on the screen is the end of a chain, and every link can lie. A few minutes with a meter at commissioning saves weeks of chasing faults that were never in the plant.

Sources mentioned: IEC 60381-1 and 60381-2 (analogue signal ranges); NAMUR NE 43 (fault signal levels, as widely published - the document itself is paid); BS EN IEC 60228 (conductor resistance); BS EN IEC 60751:2022 (platinum sensors). The chart and diagram figures are worked from those standards; follow the data sheet for the sensor and transmitter fitted.