Five trend charts that find the waste - and how to read each one

Most BMS trend logs are read one line at a time, scrolling back through a week of supply temperatures to see whether anything looks odd. That finds the faults someone already suspects. Arranging the same data into a handful of standard charts finds the ones nobody suspected - and turns them into pictures a client can understand in a few seconds.

This article is for integrators and service engineers who already collect trends and want more out of them. It covers five chart forms, what each one is good at, the patterns to look for and the checks to make before a finding goes in a report. It is a companion to Fault detection on a BMS, which sets out the rules an analytics engine runs. This one is about reading the charts yourself.

Why the shape matters more than the number

A trend line shows what happened. A chart form shows a pattern, because it puts the samples side by side in a way that makes the normal shape obvious and anything else stand out. Public programmes built on this idea have found operational problems in almost every building they looked at. Pacific Northwest National Laboratory's analysis of trend data from 151 US buildings found typical operational problems in almost every one of them (PNNL), and its Building Re-tuning training teaches exactly this kind of trend-led review. Those are North American samples, but the plant and the faults are familiar.

Each chart below needs only data most sites already log. None needs special software, though a tool that draws them quickly makes a review practical across a portfolio.

1. The carpet plot - when energy is used

A carpet plot lays half-hourly or hourly data out as a grid: one row per day, one column per time of day, the colour of each cell showing how much energy was used or how hard a plant item ran. Occupied hours show as a solid band across the weekdays. Nights, weekends and holidays should be dark.

Read it for shape before reading any number:

The carpet plot shows when, not why. Before changing a time programme, check the building's real hours with the client - cleaners, security and events all count. CIBSE TM39 covers the metering and monitoring that feeds it (CIBSE TM39). There is no widely accepted UK benchmark for the out-of-hours share, so compare a building with itself over time.

2. The energy signature - how the building answers the weather

An energy signature plots each day's or week's energy against the average outside temperature for the same period. A heated building gives a cloud of points that rises as it gets colder, then flattens above the temperature where no heating is needed. Fit a sloping line and a flat line that meet at a change point, and you have three readings:

A high flat line means a high baseload. A balance point that is too warm suggests heating enabled in mild weather or a summer lockout set wrongly. Days well above the line are worth looking at one by one - they are often overrides or plant left running after a fault. CIBSE TM41 explains degree days and base temperatures (CIBSE TM41), and ASHRAE Guideline 14 describes how to judge whether such a model is good enough to measure savings against. Limits of about ±5% NMBE and 15% CV(RMSE) on monthly data are widely quoted from it (UCL paper quoting Guideline 14) - but passing them does not prove a model right, so look at the scatter around the line as well.

Proving savings takes the fitted model on into baselines and CUSUM tracking.

3. Valve against coil delta-T - what the coil really delivers

Plot each trend sample with the commanded valve position along one axis and the temperature difference across the coil up the other - water in against water out, or air on against air off where there are no water sensors. A healthy coil gives a curve that rises as the valve opens and levels off near its design difference. Where there is no flow meter, which is most sites, this plot does much of a meter's job.

Three faults stand out:

Lawrence Berkeley National Laboratory's study of fault data from 317 US buildings found coil valve faults among the common and persistent air handling unit problems (Crowe and others, LBNL, 2023). Confirm before reporting: check the sensors against a reference (see Signals that lie for the wiring faults that fool them), watch the actuator stroke, and measure the pipe downstream of a shut valve.

4. AHU states on the psychrometric chart - what each section does to the air

Take outside, return, mixed, off-coil and supply conditions at the same moment and plot them on a psychrometric chart. Each process becomes a line: mixing, heating, cooling and drying. Hour by hour the points show whether the sequence is doing what the strategy says.

Published rule sets work out the operating state first - heating, cooling, economising - from the valve and damper commands, then apply only the checks that make sense in that state. NIST's air handling unit performance assessment rules do this (NISTIR 6964). Do the same by eye, and you will not report a normal mode as a fault.

5. The alarm Pareto - where the noise comes from

Rank alarm sources by how many alarms each raised over a month, worst first, with a line showing the running share of the total. On most sites a handful of points make most of the alarms - a sensor flickering across a limit, a status that drops out at every start. Fix those few causes and the operators start trusting the alarms that remain.

The figures usually quoted come from industrial control rooms. EEMUA Publication 191 judges alarm load per operator (EEMUA 191), and IChemE guidance quotes a flood as more than 10 new alarms in ten minutes (IChemE). A BMS is not a refinery, so adapt rather than copy, and never suppress a life-safety or critical alarm to improve the numbers.

A sixth view for control faults

One more chart deserves a mention: the overlay trend, with a loop's setpoint, measured value and output on one axis at a fast sample rate. A smooth regular swing is usually tuning; a sawtooth, where the output ramps and the value jumps, is a valve or damper sticking, and no retuning will fix it. On/off plant leaves a square wave instead - count the starts per hour.

Turning charts into findings

A chart is evidence, not a conclusion. For each finding, keep the chart, the check that confirmed it and the likely cause, and agree the fix with the client before anything changes. Then draw the same chart again a few weeks later. A carpet band pulled back to its proper edges, or a signature with a lower flat line, is one of the clearest before-and-after pictures you can put in front of a client.

Start small: one building, a month of data, all five charts. The patterns repeat from site to site, and after a few reviews the faults are recognisable at a glance.

Sources mentioned: PNNL analysis of operational problems in 151 US buildings and its Building Re-tuning programme; CIBSE TM39 and TM41; ASHRAE Guideline 14 (limits as quoted in a UCL conference paper); LBNL fault prevalence study (Crowe and others, 2023); NISTIR 6964; EEMUA Publication 191; IChemE alarm management guide. The US studies are North American samples. The data in the diagram is illustrative, not a real site.