Retail, hotels and warehouses - where the BMS still earns its keep

Retail, hotels and logistics are big users of energy, but they are awkward markets for a controls integrator. The largest single load in a supermarket is usually run by someone else's controller. A hotel's energy follows guests rather than a timetable. A warehouse may have a very simple BMS, or none, and a roof full of heaters. And almost every published savings figure in these sectors comes from a company selling the product.

So this article is about method. It covers where the energy goes in each building type, the controls levers that are well understood, and how to talk about savings when the independent evidence is thin. Where a figure comes from a vendor, it says so.

Where the energy goes

The UK benchmarks most people still use are in CIBSE TM46 (2008). They are old, and the CIBSE document is paid, so the figures below were read from a published copy of its table - check them against TM46 before relying on them in a report.

Typical annual energy use by building type - CIBSE TM46 - kWh per m2 of floor area a year
Electricity
General office95
General retail165
Retail warehouse70
Storage warehouse or depot35
Refrigerated warehouse145
Fossil fuel (heating)
General office120
General retail0
Retail warehouse170
Storage warehouse or depot160
Refrigerated warehouse80

TM46 dates from 2008. In a storage warehouse heating is most of the energy, which is why heating control, destratification and dock doors come first. Measured landlord benchmarks (REEB) are added once read from the published charts.

TM46 typical energy use by building type, read from a published copy of the table - check against CIBSE TM46 before use. Source: CIBSE TM46 (2008), figures read from a published copy of its benchmark table. Flags: UK, Check against CIBSE TM46, 2008 benchmarks. Links: CIBSE TM46.

The pattern is the useful part. A general shop is almost all electricity. A storage warehouse is mostly heating: 160 of its 195 kWh per square metre in TM46 comes from fossil fuel. A refrigerated warehouse is mostly electricity again. The Better Buildings Partnership publishes more recent measured benchmarks for offices and shopping centres from landlord data each year (REEB benchmarks), which are worth reading directly for those building types.

Retail - the refrigeration boundary

In large UK retail chains, refrigeration is about 42% of electricity use, ranging from 29% in hypermarkets to 60% in small stores (International Journal of Refrigeration, 2023). It is usually controlled by a dedicated refrigeration controller, maintained by a refrigeration contractor with F-gas certification. That boundary matters, and the integrator should respect it.

What the BMS can do is everything around it:

The F-gas rules phase HFC use down by 79% by 2030, so some refrigerants will become scarcer and dearer (SEPA / Environment Agency leaflet). Leak monitoring through the BMS is a natural addition, but work on the refrigeration circuit itself stays with certified refrigeration engineers.

Hotels - follow the guests

No independent published figure for HVAC's share of hotel energy was found. The large North American recommissioning dataset found its lowest median saving in lodging - about 3% - which is a useful reminder that hotels are not an easy win (Crowe et al. 2020).

The method is clear even where the numbers are not:

Warehouses - heat, height and doors

In a heated warehouse, heating is most of the bill, and three things decide how much is wasted.

Talking about savings in these sectors

The honest position is that independent UK measured evidence for retail, hotel and warehouse controls optimisation is thin, and most published percentages come from vendors. That is not a reason to avoid the work. It is a reason to sell it differently:

Large retail, hotel and logistics groups will be preparing for ESOS Phase 4 through 2026 and 2027, and their audit reports will list controls recommendations - a ready-made starting point. ESOS Phase 4 and demand flexibility covers that route, and Proving savings covers the measurement.

Shaping the offer

A multi-site service for these sectors might include a schedule and out-of-hours review per site, refrigeration alarm integration (with the refrigeration contractor), unsold-room setback for hotels, destratification and dock door interlock checks for warehouses, and a portfolio report comparing sites against each other. Comparing a chain's own sites is often more persuasive than any benchmark.

Related tools and training: the carpet plot and load profile, out-of-hours running cost, degree-day normalisation and alarm load worksheet tools are in tecTools, and the Servicing and optimising an existing BMS course is in tecTraining.

Sources mentioned: CIBSE TM46 (2008, figures read from a published copy of its table); Better Buildings Partnership REEB benchmarks; International Journal of Refrigeration (2023); EIA report on supermarket refrigeration (advocacy source); SEPA and Environment Agency F-gas leaflet; Crowe et al. 2020 (North American); a door maker's case study (vendor estimate). Results depend on the building, its use and its plant.